Tepco о дозах радиации

Mar 28, 2011 10:24

Хотя тут  я инфо проапдейтил - замечу, что данные про превышение нормы в 10 млн раз ( более одного зиверта в час) Tepco отозвала, назвав их ошибочными.
Вчера по радио ( NDR1) сообщали про прев. нормы в 300 тыс. раз (т.е 30 миллизивертов). Сегодня уж СМИ сообщают, что ТЕПКО дает инфо про более чем 100 тыс раз.
http://www.welt.de/newsticker/dpa_nt/infoline_nt/brennpunkte_nt/article12983414/Kernschmelze-in-Japan-Regierung-kritisiert-Tepco.html

"Der Betreiber des Unglückskraftwerks, Tepco, hat inzwischen seine Angaben zur Verseuchung des Wassers korrigiert. Das Unternehmen spricht jetzt noch von einer 100 000-fach höheren Radioaktivität als normal. Zuvor hatte der Energiekonzern erst gemeldet, die Strahlung sei zehn Millionen Mal höher als sonst - dann hatte Tepco diese Zahl zurückgezogen, ohne neue Werte zu nennen."

(Tepco скорректировал данные о загрязнении воды, сейчас идет речь о 100 000 кратном превышении нормы. Ранее енейрг. концерн сообщил о прев. нормы в 10 млн раз. Затем Tepco отозвал данные, не назвав новых данных")

P.S Нек. инфо про облучение рабочих на реакторе :
http://www.tepco.co.jp/en/press/corp-com/release/11032802-e.html

Press Release (Mar 28,2011)
Plant Status of Fukushima Daiichi Nuclear Power Station (as of 12:00 AM Mar 28th)

[No update from the last release issued at 8:30 pm, March 27th] All 6 units of Fukushima Daiichi Nuclear Power Station have been shut down. Unit 1 (Shut down) - Explosive sound and white smoke were confirmed after the big quake occurred at 3:36 pm Mar 12th. It was assumed to be hydrogen explosion. - At approximately 2:30 am on March 23rd, seawater was started to be injected to the nuclear reactor through the feed water system. - At approximately 10:50 am on March 24th, white fog-like steam arising from the roof part of the reactor building was observed. - At approximately 11:30 am on March 24th, lights in the main control room was restored. - We had been injecting sea water into the reactor, but from 3:37 pm on March 25th, we started injecting fresh water into it. Unit 2 (Shut down) - At approximately 6:00 am on March 15th, an abnormal noise began emanating from nearby Pressure Suppression Chamber and the pressure within this chamber decreased. - At 6:20 pm on March 21st, white smoke was confirmed arising from the top of the reactor building. As of 7:11 am on March 22nd, smoke decreased to the level to nearly non-existent. - We have been injecting sea water into the reactor, but from 10:10 am on March 26th, we started injecting fresh water (with boric acid) into it. - At approximately 4:46 pm on March 26nd, the light in the main control room was turned on. - Previously, we have been injecting fresh water in to the reactor utilizing fire pump, however, we have switched over to utilizing temporary electrical pump from 6:31 pm on March 27th. Unit 3 (Shut down) - Explosive sound and white smoke were confirmed at 11:01am March 4th. It was assumed to be hydrogen explosion. - At 8:30am on March 16th, fog like steam was confirmed arising from the reactor building. - At approximately 6:15 am on March 17th the pressure of the Suppression Chamber has temporarily increased. We were preparing to implement measures to reduce the pressure of the reactor containment vessel (partial discharge of air containing radioactive material to outside) in order to fully secure safety. However, at present, it is not a situation to immediately implement measures and discharge air containing radioactive material to outside. We will continue to monitor the status of the pressure of the reactor containment vessel. - At approximately 4:00 pm, March 21st, light gray smoke was confirmed arising from the floor roof of the Unit 3 building. On March 22nd, the color of smoke changed to somewhat white and it is slowly dissipating. - At approximately 10:45 pm on March 22nd, the light in the main control room was turned on. - At around 4:20 pm on March 23rd, our staff confirmed light black smoke belching from the Unit 3 building. At approximately 11:30 pm on March 23rd and 4:50 am on March 24th, our employee found no signs of smoke. - We had been injecting sea water into the reactor pressure vessel, but from 6:02 pm on March 25th, we started injecting fresh water into it. Unit 4 (outage due to regular inspection) - At approximately 6 am on March 15th, we confirmed the explosive sound and the sustained damage around the 5th floor rooftop area of the Nuclear Reactor Building. - On March 15th and 16th, we respectively confirmed the outbreak of fire at the 4th floor of the northwestern part of the Nuclear Reactor Building. We immediately reported this matter to the fire department and the related authorities. TEPCO employees confirmed that each fire had already died down by itself. - At this moment, we do not consider any reactor coolant leakage inside the reactor happened. Unit 5 (outage due to regular inspection) - Sufficient level of reactor coolant to ensure safety is maintained. - At 5 am, March 19th, we started the Residual Heat Removal System Pump (C) in order to cool the spent fuel pool. - At 2:30 pm, March 20th, the reactor achieved reactor cold shutdown. At around 5:24 pm on March 23rd, when we switched the temporary Residual Heat Removal System Seawater Pump, it has stopped automatically. At around 4:14 pm, March 24th we replaced the pump, and restarted cooling of reactor at around 4:35 pm. - At this moment, we do not consider any reactor coolant leakage inside the reactor containment vessel happened. Unit 6 (outage due to regular inspection) - Sufficient level of reactor coolant to ensure safety is maintained. - We completed the repair work on the emergency diesel generator (A). - At 10:14 pm, March 19th, we started the Residual Heat Removal System Pump (B) of Unit 6 in order to cool the spent fuel pool. - At 7:27 pm, March 20th, the reactor achieved reactor cold shutdown. - In relation to the two seawater side pumps of the Residual Heat Removal System, we switched the power source from temporary to permanent at 3:38 PM and 3:42PM, Mar 25 respectively. - At this moment, we do not consider any reactor coolant leakage inside the reactor containment vessel happened. Today's work for cooling the spent fuel pools - We are considering further spraying subject to the conditions of spent fuel pools. Casualty - 2 workers of cooperative firm were injured at the occurrence of the earthquake, and were transported to the hospital on March 11th. - Presence of 2 TEPCO employees at the site is not confirmed on March 11th. - 1 TEPCO employee who was not able to stand by his own holding left chest with his hand, was transported to the hospital by an ambulance on March 12th. - 4 workers were injured and transported to the hospital after explosive sound and white smoke were confirmed around the Unit 1on March 12th. - 1 subcontract worker at the key earthquake-proof building was unconscious and transported to the hospital by an ambulance on March 12th. - The radiation exposure of 1 TEPCO employee, who was working inside the reactor building, exceeded 100mSv and he was transported to the hospital on March 12th. - 2 TEPCO employees felt bad during their operation in the central control rooms of Unit 1 and 2 while wearing full masks, and were transferred to Fukushima Daini Nuclear Power Station for consultation with a medical advisor on March 13th. - 11 workers were injured and transported to Fukushima Daini Nuclear Power Station etc. after explosive sound and white smoke were confirmed around the Unit 3. One of the workers was transported to the Fukushima Medical University Hospital on March 14th. - At approximately 10 pm on March 22nd, 1 worker who had been working on setting up a temporary power panel in the common pool was injured and transported to Fukushima Daini Nuclear Power Station where the industrial doctor is. - At approximately 1:30 am on March 23rd, 1 worker who had been working on transporting a temporary power panel in the common pool was injured and transported to Fukushima Daini Nuclear Power Station where the industrial doctor is. - On March 24th, it was confirmed that 3 workers from cooperative companies who were in charge of cable laying work in the 1st floor and the underground floor of turbine building were exposed to the radiation dose of more than 170 mSv. 2 of them were confirmed that their skins on legs were contaminated. Although they were decontaminated, since there was a possibility of beta ray burn injury, they were transferred to Fukushima Medical University Hospital. The third worker was also transferred to Fukushima Medical University Hospital on March 25th. After that, the 3 workers were transferred to National Institute of Radiological Sciences in Chiba Prefecture. Regarding this event, TEPCO has reported to the related government ministries and agencies on measures to be taken to assure appropriate radiation dose control and radiation exposure related operations. Before today's restoration work, we will make notification to the concerned parties and continue to take all possible measures to future management. Others - We measured radioactive materials (iodine etc.) inside of the nuclear power station area (outdoor) by monitoring car and confirmed that radioactive materials level is getting higher than ordinary level. As listed below, we have determined that specific incidents stipulated in article 15, clause 1 of Act on Special Measures Concerning Nuclear Emergency Preparedness (Abnormal increase in radiation dose measured at site boundary) have occurred. · Determined at 4:17 pm Mar 12th (Around Monitoring Post 4) · Determined at 8:56 am Mar 13th (Around Monitoring Post 4) · Determined at 2:15 pm Mar 13th (Around Monitoring Post 4) · Determined at 3:50 am Mar 14th (Around Monitoring Post 6) · Determined at 4:15 am Mar 14th (Around Monitoring Post 2) · Determined at 9:27 am Mar 14th (Around Monitoring Post 3) · Determined at 9:37 pm Mar 14th (Around main entrance) · Determined at 6:51 am Mar 15th (Around main entrance) · Determined at 8:11 am Mar 15th (Around main entrance) · Determined at 4:17 pm Mar 15th (Around main entrance) · Determined at 11:05 pm Mar 15th (Around main entrance) · Determined at 8:58 am Mar 19th (Around MP5) From now on, if the measured figure fluctuates and goes above and below 500 micro Sv/h, we deem that as the continuous same event and will not regard that as a new specific incidents stipulated in article 15, clause 1 of the Act on Special Measures Concerning Nuclear Emergency Preparedness (Abnormal increase in radiation dose measured at site boundary) has occurred. In the interim, if we measure a manifestly abnormal figure and it is evident that the event is not the continuous same event, we will determine and notify. - The national government has instructed evacuation for those local residents within 20km radius of the periphery and evacuation to inside for those residents from 20km to 30km radius of the periphery, because it is possible that radioactive materials are discharged. - At approximately 10am on March 15th, we observed 400mSv/h at the inland side of the Unit 3 reactor building and 100mSv/h at the inland side of the Unit 4 reactor building. - At around 10:37 am March 21st, water spraying to common spent fuel pool and finished at 3:30 pm (conducted by TEPCO). - At around 3:37 pm, March 24th, electricity supply to common spent fuel pool has started from external power source. At around 6:05 pm, fuel pool cooling pump was started to cool the pool. - We found no signs of abnormal situation for the casks by visual observation during the patrol activity. A detailed inspection is under preparation. - At Units 5 and 6, in order to prevent hydrogen gas from accumulating within the buildings, we have made three holes on the roof of the reactor building for each unit. - In total 12 fire engines are lent for the water spraying to the spent fuel pools and water injection to the nuclear reactors by various regional fire departments* as well as Tokyo Fire Department. Also, instruction regarding the setting and operation of large scale decontamination system was provided by Niigata City Fire Headquarter and Hamamatsu City Fire Headquarter. *: Koriyama Fire Department, Iwaki Fire Brigade Headquarters, Fire Headquarters of Sukagawa District Wide Area Fire-fighting Association, Yonezawa City Fire Headquarters, Utsunomiya City Fire Headquarters, Fire Headquarters of Aizu-Wakamatsu wide area municipal association, Saitama City Fire Bureau, and Niigata City Fire Bureau. - By March 22nd, Units 1 through 6 were started to be energized from the external power source. - We will continue to take all measures to ensure the safety and to continue monitoring the surrounding environment around the Power Station.

japan, катастрофы

Previous post Next post
Up